The Reduced Pressure Zone Valve Assembly (Figure 2) consists of two independently operating check valves just like the Double-Check as well as a hydraulically operated differential relief valve located below the first check valve.
Now consider a full failure of the #2 check valve, like one that might occur if the device is knocked out of round or has a mechanical failure. It’s essentially the same event with the exception that due to the larger valve opening, there is actually a higher flood rate. Now you have water flowing through the relief valve at full head pressure. Again, if this is a large or multi-story building, that’s a lot of water very fast.
backflowtesting是什么
Watch the video below for an example of RPZ flooding and to see just how much water is discharged when a small amount of debris becomes lodged in the device.
This hydraulic valve and its placement makes the RPZ virtually fail-safe but it comes at a cost to the area around the device.
Zurn wilkins
WattsBackflow preventer
The main thing to take away from this is that both backflow prevention device types perform the same function when they are operating properly, but only the RPZ is designed to protect the public water supply by disposing of any backwards-flowing water if any of the check valves or the relief valve fails.
Consider a flow-stop situation, like one that might naturally occur at the end of the day (Figure 4). If you look closely, you can see that a small pebble has lodged in the #2 check valve. Now imagine some sort of back siphon event over night. Perhaps a nearby building fire leaches the water back with the draw of a fire hydrant; or a pump station fails; or a water main breaks. Because the #2 check valve is not closing, all the water that has been delivered to the building will continue to flow out the relief valve until the private lines are cleared. If this is a four story building, that’s a lot of water.
You’ve heard these phrases and acronyms repeatedly. If you are a designer, you feel sure that you are expected to know what they mean. Here’s a quick rundown on what they are and how they differ.
How do you determine hazard? The simple answer is that the purveyor determines it, but every jurisdiction is different. Every city has its own list of named examples for what constitutes the hazard threshold. Here is an example from Washington DC. They also stipulate that if the anticipated use, as you know it, is not named explicitly, then they reserve the right to make the decision during plans review. It’s also important to understand that you cannot, as a designer, over-protect the incoming water service. This means there is no penalty for providing the higher degree of protection.
The AutoHot EMS can be installed onto your multifamily or commercial building’s central hot water system at low or NO cost...
backflowpreventer中文
Want to monitor your system remotely and manager energy use? Want to be notified when system failure occurs? AutoHot has you covered
Optimize your hot water system with AutoHot controls. We have solutions for all types of buildings: Residential, Multifamily, or Commercial. New construction or retrofit. We are dedicated to researching and developing the latest hot water technology that saves water and energy, and improves the service of hot water.
When a flow stop occurs, both check valves close. At that moment, the relief valve opens and evacuates the water between the valves. (Figure 3) Some think that this event defines the limit of how much water can ever flow from the RPZ into a drain. This is not so.
A designer may specify one of 2 types of backflow prevention devices. First, the Double-Check Valve Assembly. This is often shortened to DC and is typically thought of as the appropriate solution for low hazard conditions. Second, the Reduced Pressure Zone Valve Assembly, often shortened to RP or RPZ, is thought of as the appropriate solution for high hazard conditions.
View your hot water system performance data in real time and analyze historical trends. Set up alert notifications to tell you when there are system failures or remind you of preventative maintenance schedules
Eliminate the wait for hot water in any plumbing system by using on-demand recirculation pumps. Works with any tank, tankless, or heat pump water heater, in any plumbing configuration
Have a question about a backflow preventer enclosure?Click the contact us button below and one of our experts will be able to help with your specific enclosure needs.
Check valve
The Double-Check Assembly (Figure 1) was developed in the 1950s for the fire industry. Any time the pressure on the property (downstream) side exceeds the pressure on the city (public) side, the two redundant check valves close stopping the backwards water flow. There are two problems with the Double-Check backflow preventer. First, no remedy exists in the event of a malfunction of the valve closures or if debris in the water line causes the valves to not close completely. Second, and this is the big problem, there is no way to know when such a failure has occurred without conducting a full test by a qualified professional. The Double-Check is a closed system. It has no method of revealing whether the internal check valves are functioning properly and no way to detect the presence of debris that is impeding full closure.
Eliminate the wait for hot water at any fixture in your house by using AutoHot's on-demand recirculation pump system, and save thousands of gallons of water per year
Optimize your commercial hot water system and reduce total water heating energy use by up to 30% or more using the AutoHot Hot Water Energy Management System (EMS)
Central to a high performing hot water system is a demand-controlled recirculation pump. Building energy codes and performance certifications are now requiring that buildings that use hot water recirculation pumps must also have demand controls to help regulate the system run time for reduced energy losses. Using and specifying the AutoHot system will help your building meet these code requirements and ensure efficient hot water delivery in any application. Look for these requirements in such new building standards such as: California Title 24 (part 6), International Energy Conservation Code (IECC), The Department of Energy Zero Energy Ready Home (ZERH) program, LEED for Homes v4 and others.