Open the upstream isolating valve and connect the high-pressure hose of the test kit to test tap one, and the low pressure hose of the test kit to test tap two. Open test taps one and two. Open test kit valve A and bleed the water through the vent hose. Close test kit valve A. Open test kit needle valve B and bleed water through the vent hose to eliminate air from the system.

To restore the double check valve to its operating condition, close test tap two and test tap three. Open test kit valves A and B, disconnect the test kit pressure hoses and open the downstream isolating valve. This restores the device to its operating condition.

To determine which valve is leaking, open test tap one. If there is a continuous discharge of water from test tap one, the upstream isolating valve is leaking.

Lf009qtleaking

To test the downstream check valve, close test tap one and test tap two, and open test kit valves A and B. Close test kit valves A and B.

Image

watts lf009-qt-s

Turn on test tap three, then bleed air through the drain line. Close test tap A, close needle valve B, then in sequence close test tap C, and the upstream isolating valve.

For the DCV test to be successful, both the upstream and downstream isolating valves must not leak, and the pressure differential across each check valve must be 7kPa or greater.

The pressure gauge will show a high reading. Open test kit valve A. Slowly open test kit valve B, and drop the gauge pressure by 20kPa.

wattslf009qt1/2 repair kit

Your pre-test checks should include; flushing and cleaning the line strainer, and opening the isolating valve where necessary.

To test the upstream check valve, close test tap three. Close test kit valve A and open test kit valve C. Disconnect the high-pressure hose from test tap three and clean the line strainer where fitted.

If the pressure on the gauge is rising, either the upstream isolating valve or the downstream isolating valve is leaking.

009 QT 1/2 Repair Kit

Image

Watts 88004110

If a reading below 7kPa is indicated, the downstream non-return valve shall be deemed to be faulty. The valve must be repaired or replaced and the test shall be repeated.

Disconnect the low pressure hose from test tap two and reconnect to test tap three. Disconnect the high pressure hose from test tap one and reconnect to test tap two.

Simply leave your comments below. If the feedback is about a bug, please provide the steps you took so we can replicate.

Slowly open test kit needle valve B and bleed water through the vent hose to eliminate air from the system. Slowly close test kit needle valve B and observe and record the reading on the differential pressure gauge.

Image

You can use CTR+V to paste a screenshot from your clipboard directly into the textarea above. Otherwise you can upload a file from your computer below.

If a reading below 7kPa is indicated, the upstream non-return valve shall be deemed to be faulty. The valve shall be repaired or replaced and the tests must be repeated.