Tekmar 356manual

Control Type: Microprocessor control, this is not a safety (limit) controlDemand: Mixing demand 24 V (ac) 2 VADimensions: 4-3/4" H x 2-7/8" W x 1-7/8" D (120 x 74 x 48 mm)Enclosure Material: White PVC plasticEnclosure NEMA Rating: NEMA 1Hydronic - HVAC Control Type: Mixing ControlPower Supply: 24 V (ac) plus / minus 10 percent, 50/60 Hz, 3 VARelay: 120 V (ac) 5 A, 1/6 hpSensor: NTC thermistor, 10 k ohms at 77 degrees F (25 degrees C plus / minus 0.2 degrees C) Beta=3892Variable Pump: 120 V (ac) 2.4 A, 1/6 hp

The Mixing Control 356 is designed to operate a mixing pump to control the temperature in a hot water heating system using Outdoor Temperature Reset. It can be used in applications ranging from in-floor radiant to commercial baseboard systems for boiler protection with full reset. This control regulates a single heating water temperature through Outdoor Temperature Reset. It provides mixing by speeding up or slowing down a single permanent capacitor (standard wet rotor) circulator.