(a) the location of appliance isolation valves and consumer piping regulators; and(b) the relevant requirements of AS/NZS 5601.1 and AS 3814.

Permanent fixed means of access should be installed where the regulator is located on a roof or at a height beyond the extent of normal steps or ladder. Fixed access is to comply with AS 1657-2013 Fixed platforms, walkways, stairways and ladders – Design construction and installation.

The purpose of this Information Sheet is to provide, for industrial and commercial installations, a consistent approach to:

The currency and accuracy of this document cannot be guaranteed once printed or saved to a storage device. If in doubt, please check the ESV website for the current version.

In many instances burners are located on top of an appliance. This may be for a number of reasons, such as the location of oven re-circulation fan and combustion chamber for compactness or floor space limitations. Spray and bake booths are a common example.

The appliance isolation valve is generally additional to the burner isolation valve located adjacent to the burner and intended for commissioning and servicing.

This bonnet and poppet assembly kit includes the parts necessary to repair or replace the bonnet and poppet assembly of a 1/2 and 3/4 inch pressure vacuum breaker. This kit consists of bonnet, O-ring, spring, E-ring, washer, stem, rubber disc and poppet. All parts are genuine and original to the valve.

Locating a gas appliance isolation valve on the top of an appliance does not enable the quick isolation of the gas supply as required by AS 3814 clause 2.9.8.3. In order to achieve compliance the gas appliance isolation valve will be required to be brought down to low level adjacent to the appliance and be clearly identified.

Locations greater than 2m above ground level will require observance of the Occupational Health & Safety Regulations 2017.

We acknowledge Victoria's Traditional Owners as the original custodians of the lands on which we work. We offer gratitude and pay respect to Elders past and present.

The location of an emergency valve for a steam boiler or hot water installation, as required by AS/NZS 5601.1 Clause 5.2.10, is based on the intent to limit the exposure of personnel to a possible steam hazard, i.e. leaking steam or steam-side explosion.

An alternative means of safe access acceptable to Energy Safe Victoria may be provided by the property owner or his representative by agreement.

All commercial / industrial installations require a means of isolation provided on the inlet connection of an appliance.

Access can be gained without hazard or undue difficulty for inspection, repair, testing, renewal, or operational purposes.

In each of the above clauses the word “accessible” is used and is a requirement in order for the installation to be compliant with the standards.