Manuals for Tekmar Products - tekmar controls
Expansion tank sizingChart
It is important to remember here that on applications like this, the larger the vessel the smoother the system will run, and less energy will be required switching the pumps on and off. Additionally, if space is a constraint, vessels can be installed in tandem on a common manifold on the discharge pipework.
The selection and sizing of vessels is very important depending on the application type and system characteristics. Many a pump has failed due to too many starts because of incorrectly specified pressure vessels, and undersized expansion vessels can cause a range of failures.
This potable water expansion tank is used on gas, oil or electric, direct-fired, residential water heater and hot water storage tank applications to absorb the increased volume of water created by thermal expansion. It also maintains balanced pressure throughout the water supply system by keeping system pressure below the T and P relief valve setting. This field-adjustable steel tank is air pre-charged at 20 psi, volume 2.1 Gal. designed with an FDA-approved polypropylene liner and Butyl rubber diaphragm, copper-lined steel and 3/4 in. male inlet connection. An expansion membrane prevents air-to-water contact in the tank ensuring a long system life. IAPMO listed and ANSI/NSF 61 certified. The maximum pressure is 150 psi (10 BAR).
Expansion tank sizingcalculator
The ‘rule of thumb’ calculation is that the pressure vessel size is equal to 6 seconds of maximum flow. For example: if the design maximum flow rate of a booster set is 3 l/s – the required vessel size would be 18 litres.
Expansion tank sizingcalculator metric
JavaScript seems to be disabled in your browser. For the best experience on our site, be sure to turn on Javascript in your browser.
Expansion tank sizingchilled water
A simple rule of thumb is 10% of the system volume – rounding up to the nearest vessel size. Allow for 10 litres per standard radiator and an additional 10 litres for a boiler. For example; a system with 10 radiators and a modern boiler would equate to an approximate system volume of 110 litres. 10% would equate to 10 litres – therefore using this calculation a 12 litre vessel would be suitable.
Heating expansion vessels are selected and commissioned taking into account three system characteristics; maximum system temperature, system volume and static head above the vessel. The system volume and operating temperature range dictates the pressure vessel size and the static system head dictates the pre-charged pressure. There are however a couple of quick simple methods to this – based on the assumption that the system is 82℃ / 71℃ flow and return and a system pressure up to 1.5 bar.
Assuming a 1.0 bar system pressure when the system is ‘cold’, the expansion vessel will normally be sized to ensure the running pressure at operating temperature rises by approx 0.5 Bar to 1.5 bar running pressure. Therefore if the pressure vessel is installed at the top of the system the pre-charge pressure of the vessel will be equal to the ‘cold-fill’ pressure (1.0 Bar). If the pressure vessel is installed at a lower point of the system the static pressure of the system above the vessel should be added to the pre-charge pressure. E.g. if the static height of the top point of the system is 5 metres above the pressure vessel, the pre-charge pressure should be 1.0 bar + 5 metres = 1.5 bar.
Another ‘rule of thumb’ method of calculating vessel size is using the boiler KW size. The method used is to allow for 1 litre capacity per kW. For example; 7kW output would equate to an 8 litre vessel.
AMTROLexpansion tank Sizingpdf
Expansion Tank SizingExcel
Copyright © 2024 Trade Pumps. All rights reserved. Tradepumps is a trading name of Dutypoint Ltd, a company registered in England and Wales No 09045694Registered office: Unit A, Quedgeley West Business Park, Gloucester, GL2 4PA, United Kingdom
To calculate what size pressure vessels you will need for a pressure boosting system, the easiest method is by taking the design flow rate of the pump or pump system.
Both the above methods tend to slightly oversize the vessel capacity. Please see below table for more accurate selections: