HighlightsSave money - up to 10% of your water billMaintenance freeEasy to install in less than 1 hourAdditional sensor valves available for homes with multiple plumbing loopsHot water WHERE you need itHot water when you need itProgrammable timer is built-in so the pump turns on only when you need itNot for use with tankless water heatersCheck compatibility to ensure it will work on your systemReliable and easy to maintain
Size the Recirculation Return Line. A sizing calculator (i.e. System Syzer) can be used to size the return line. For 1.87 gpm we would choose a ¾” copper pipe. The friction loss for this diameter supply pipe will be about 1.4 ft per 100 ft., according to the System Syzer.
With this information show here we can determine our required recirculation flow rate, size our recirculation pipe, and select the right size pump.
1. The maximum temperature difference (Delta T) that you are willing to tolerate between the heater and the last fixture. This is typically 10°F, 15°F or 20°F.
Determine Pump Head & Select Pump. Given that our recirculation line is 300 feet in lenth, and our flow rate is 1.9 gpm (rounded up), we must calculate the total friction loss:
The return portion of the recirculation piping need not be considered, as that heat loss occurs after the last fixture, and will not impact the supply water temperature.
First, it is important to remember the objective of your design, which is to overcome the heat loss in the pipe between the water heater and the most distant fixture during periods of no draw. Think of the recirculating portion of the system as an extension of the hot water storage. The greater the storage volume, the more BTUs that are required to keep the water hot. How many BTUs depends on the following factors:
Never wait for hot water again; The Watts Hot Water Recirculating Pump provides hot water at every faucet or shower when needed, eliminating wasted water. It is easy to install on any water system and requires no additional piping. The unique design of the pump ensures quiet, maintenance-free operation. The system includes a built-in 24 hour, a dual setting programmable timer to activate the pump only when needed.
Designing a domestic hot water recirculation system is not typically difficult. In fact, we see the exact same model recirculation pump used in application after application without incident, as this one pump is typically able to meet the minor head and flow requirements of most recirculation systems. That said it is important to work through the proper design procedures for any recirculation system. A little time up front can save a lot time (and money) after the fact.
For this design, a 10°F temperature drop has been chosen. Table 2 shows us what the BTU/GPM relationship is for the various temperature drops.
With this information we can complete our calculation to determine the necessary recirculation flow rate required to overcome the heat loss in this particular system. Since 1 gpm will convey 5000 BTUH at a 10°F ∆T, the recirculation flow rate is:
JMP is excited to announce our new technical HVAC magazine! It is a great resource to get bite-sized educational pieces similar to the content featured in our seminars. Register to have the latest blog sent to your email address.
Admittedly, it’s quite a few calculations to get to the definitive pump size and sizing programs are available to do most of the work. Still, it’s important to understand the logic that goes into a properly designed hot water recirculation system, especially as system designs become more complex, as we shall see in some up coming blogs.
Determine Recirculation Rate. The recirculation rate is based on the heat loss that would occur between the heater and farthest fixture at no draw. To determine this value we consult a piping heat loss chart (Table 1). Remember, the values listed here are per 100 ft. so we apply our actual values, we will divide by 100.
Next, based on using insulated copper tube, with 25 ft. length between risers, we can manually calculate the total supply line heat loss from the heater to the farthest riser, coming up with a total heat loss of 9320 BTUHs.
2. The return portion of the recirculation piping need not be considered, as that heat loss occurs after the last fixture, and will not impact the supply water temperature.